Outback Power Systems Power Supply FW IOB D 120VAC User Manual |
T M
FW-IOB-D-120VAC
Input/Output/Bypass Assembly
Installation Instructions
Requirements and Warnings
The OutBack FW-IOB-D-120VAC is intended as a system compo-
nent and is included in a listing by ETL as indoor enclosures to UL
standard UL 508A Industrial Control Panels.
This enclosure is intended for battery circuits configured for 12 to
48 volts nominal.
Grounding Instructions – Each enclosure should be connected to
a grounded, permanent wiring system. For most installations, the
negative battery conductor should be bonded to the grounding
system at one (and only one) point in the DC system. All instal-
lations must comply with all national and local codes and ordi-
nances. System grounding as required by the National Electric
Code, ANSI /NFPA 70-1996, is the responsibility of the system
installer.
The equipment ground is marked with this symbol:
2
FW-IOB-D-120VAC Parts List
AC Breaker Bypass
Slide Plate
Breaker Label Set
Black Terminal Bus
Bar Insulators
White Terminal
Bus Bar Insulators
AC Breakers
Bus Bars
Hardware Kit
Ground Conductor
(Green)
Neutral Conductor
(White)
Positive Conductor
(Black)
Figure 1: FW-IOB-D-120VAC
3
AC OUT
HOT LEG 1,
BLACK
AC IN
HOT LEG 1,
BLACK
INSULATORS
INSULATORS
GROUND
BUS BAR
AC NEUTRAL
INPUT AND
OUTPUT,
WHITE
INSULATORS
NOTE: Use 10-32 X 7/16 self-tapping stainless steel fasteners to
secure this hardware.
Figure 2: Placement of Bus Bars
4
Figure 3: Sample Wiring Diagram
5
Installing the FW-IOB-D-120VAC
Dual-Pole Bypass Breaker Output Breakers Input Breakers
(installed upside down)
Figure 4: AC Breaker Installation for FW-IOB-D-120VAC
To install the FW-IOB-D-120VAC:
• Remove the appropriate quantity of breaker knockouts from the
breaker bracket.
• Pull the yellow tabs out from each breaker.
• Install the breakers on the din rail to approximately match the
openings in the breaker bracket.
• Hold the breaker bracket loosely against the breakers on the din rail;
move the breakers as needed so they line up with the openings in
the breaker bracket.
• With the breakers positioned properly, lock the yellow tabs to secure
the breakers to the din rail.
• Install the AC Breaker Bypass Slide Plate (see Figure 5).
6
Installing the AC Breaker Bypass Slide Plate
Figure 5: AC Breaker Bypass Slide Plate Installation
Parts:
1. 8-32 X .75 Machine Screw (2)
2. Nylon Washer (4)
3. 8-32 Nylock Nut (4)
4. AC Breaker Bypass Slide Plate (1)
5. FLEXware AC Breaker Bracket (1)
To Assemble:
1. Remove necessary circuit breaker knockouts (per IOB kit).
2. Install AC Breaker Bypass Slide Plate and fasteners as shown in
Figure 5.
3. Do not over tighten the Nylock nuts. Overtightening can
cause the AC Breaker Bypass Slide Plate to bind.
Corporate Office
European Sales Office
C/ Castelló, 17
08830 - Sant Boi de Llobregat
BARCELONA, España
+34.93.654.9568
19009 62nd Avenue NE
Arlington, WA USA
(+1) 360-435-6030
900-0068-01-00 REV D
|